• IndusKey IK1105 Fire Control Solenoid Valve, Manual Override, Brass/SS Bodyv
  • IndusKey IK1105 Fire Control Solenoid Valve, Manual Override, Brass/SS Bodyv

IndusKey IK1105 Fire Control Solenoid Valve, Manual Override, Brass/SS Bodyv

No.IK1105
Fire control solenoid valve for water with manual override shut-off. Maintains open when de-energized, 0.05-1.6MPa, 3/8"-2", NBR/EPDM/VITON seals, brass or SS body, IP65 coil 20VA/18W.
  • IndusKey IK1105 Fire Control Solenoid Valve, Manual Override, Brass/SS Bodyv

Description

1. Product Overview

The IndusKey IK1105 is a fire control solenoid valve for water service, fitted with a manual override for local shut-off. Designed for fire fighting systems, the valve maintains an open position when de-energized — ensuring water supply continuity in the event of power failure — and can be closed locally via the manual override knob without electrical actuation.
Available with brass or stainless-steel bodies and seven orifice sizes from 12 mm to 50 mm (ports 3/8" to 2"), the IK1105 covers an operating pressure range of 0.05–1.6 MPa with NBR, EPDM or VITON seal options up to 150°C. The IP65-rated S21B coil (20 VA AC / 18 W DC, 100% ED) with universal AC/DC voltage options makes the IK1105 ready for fire sprinkler lines, deluge valve control, hose reel systems and industrial fire protection installations.

2. Working Principle

The IK1105 is a fire control solenoid valve supplied with an S21B coil:
  1. De-energized open (fail-safe) — The valve maintains an open position when de-energized, guaranteeing water flow during a fire event even if the electrical supply fails. ⚠️(命名说明见文末)
  2. Energized control — Applying voltage to the coil actuates the valve per the fire control logic of the installation.
  3. Manual override — A mechanical override knob on the valve body allows direct local shut-off without electrical actuation — essential for maintenance, testing and emergency isolation.
  4. Sealing — NBR (−10 ~ +80℃), EPDM (−30 ~ +120℃) or VITON (−30 ~ +150℃) seals are selected to suit the operating temperature, while the stainless-steel internals (SS304 armature tube, SS430F plunger/stop) ensure corrosion resistance in water service.

3. Key Features & Competitive Advantages

A. Manual Override Shut-Off

  • Direct local override for valve isolation without power — mandatory for fire system maintenance and testing.

B. De-Energized Open — Fail-Safe Fire Design

  • Maintains open when de-energized, ensuring water supply during power failure events.

C. Fire System Ready

  • Purpose-specified for fire fighting applications: sprinkler lines, deluge control and hose reels.

D. Broad Line Sizes

  • Seven sizes: ports 3/8", 1/2", 3/4", 1", 1-1/4", 1-1/2", 2" with orifices 12–50 mm (Cv 4.5–48).

E. High Pressure Rating

  • Operating range 0.05–1.6 MPa (16 bar) across the entire series.

F. Three Seal Options

  • NBR, EPDM and VITON to 150°C — matched to installation temperature class.

G. Dual Body Materials

  • Brass or stainless-steel body for different corrosion environments.

H. Flexible Connections

  • BSPP, BSPT, NPT and flange ends (UNF optional).

I. IP65 Coil

  • S21B coil: 20 VA (AC) / 18 W (DC), 100% ED continuous energization, IP65 enclosure.

4. Technical Specifications

5. Applications

The IndusKey IK1105 is engineered for fire protection and water control duties:
  • Fire Fighting Systems: Main and zone isolation valves in fire protection networks.
  • Fire Sprinkler Lines: Wet/dry sprinkler system water supply control.
  • Deluge Valve Control: Pilot and control circuits for deluge systems.
  • Hose Reel Systems: Water supply switching for fire hose reel installations.
  • Industrial Fire Protection: Fire water circuits in petrochemical, power, warehouse and manufacturing facilities.
  • Water Control Circuits: General high-pressure water isolation requiring manual override capability.

6. Selection, Ordering & Installation Guidelines

Model Code System

The full valve is configured by a 7-field code — example: IK1105-32GSN S21B1 (32mm orifice, 1-1/4" G-thread, stainless steel body, NBR seal, S21B coil, AC220V)
Note: BSPT, flange and UNF connections are also available — confirm at order.

Selection

  • Function check: Confirm the required de-energized state with your fire system design — the IK1105 maintains open when de-energized per manufacturer specification.
  • Pressure: Full series 0.05–1.6 MPa; verify minimum system pressure ≥ 0.05 MPa.
  • Temperature: NBR (80°C) / EPDM (120°C) / VITON (150°C).
  • Body: Brass for standard installations; stainless steel for corrosive or coastal environments.
  • Size: Match orifice/port to flow (Cv table) and check A/B/C/D dimensions for installation clearance.

Installation

  • Orientation: Coil upright preferred; observe flow-direction arrow.
  • Manual override access: Position the valve so the override knob remains accessible for emergency operation and testing.
  • Piping: Flush pipelines before commissioning; fit a strainer upstream to protect the seat from debris — critical in fire systems where reliability is paramount.
  • Protection: IP65 coil suits indoor and outdoor installation; verify the installation meets local fire codes (the valve complements, not replaces, listed fire protection components).

Operation & Maintenance

  • 100% ED rated for continuous energization.
  • Regular functional testing is essential in fire service: exercise the manual override and verify the de-energized open state per the fire system's inspection schedule.
  • Inspect seals and internals per system maintenance plans; VITON seals extend intervals in high-temperature zones.

Download