1. Product Overview
The IndusKey IK1105 is a fire control solenoid valve for water service, fitted with a manual override for local shut-off. Designed for fire fighting systems, the valve maintains an open position when de-energized — ensuring water supply continuity in the event of power failure — and can be closed locally via the manual override knob without electrical actuation.
Available with brass or stainless-steel bodies and seven orifice sizes from 12 mm to 50 mm (ports 3/8" to 2"), the IK1105 covers an operating pressure range of 0.05–1.6 MPa with NBR, EPDM or VITON seal options up to 150°C. The IP65-rated S21B coil (20 VA AC / 18 W DC, 100% ED) with universal AC/DC voltage options makes the IK1105 ready for fire sprinkler lines, deluge valve control, hose reel systems and industrial fire protection installations.
2. Working Principle
The IK1105 is a fire control solenoid valve supplied with an S21B coil:
-
De-energized open (fail-safe) — The valve maintains an open position when de-energized, guaranteeing water flow during a fire event even if the electrical supply fails. ⚠️(命名说明见文末)
-
Energized control — Applying voltage to the coil actuates the valve per the fire control logic of the installation.
-
Manual override — A mechanical override knob on the valve body allows direct local shut-off without electrical actuation — essential for maintenance, testing and emergency isolation.
-
Sealing — NBR (−10 ~ +80℃), EPDM (−30 ~ +120℃) or VITON (−30 ~ +150℃) seals are selected to suit the operating temperature, while the stainless-steel internals (SS304 armature tube, SS430F plunger/stop) ensure corrosion resistance in water service.
3. Key Features & Competitive Advantages
A. Manual Override Shut-Off
B. De-Energized Open — Fail-Safe Fire Design
C. Fire System Ready
D. Broad Line Sizes
-
Seven sizes: ports 3/8", 1/2", 3/4", 1", 1-1/4", 1-1/2", 2" with orifices 12–50 mm (Cv 4.5–48).
E. High Pressure Rating
F. Three Seal Options
G. Dual Body Materials
H. Flexible Connections
I. IP65 Coil
4. Technical Specifications
| Configuration |
|
| Valve Type |
Fire control solenoid valve |
| Function |
Normally closed (per catalogue); maintains open when de-energized — see note below |
| Port Size |
3/8", 1/2", 3/4", 1", 1-1/4", 1-1/2", 2" |
| Connection |
BSPP, BSPT, NPT, flange, UNF |
| Orifice |
12 / 15 / 20 / 25 / 32 / 40 / 50 mm |
| Models |
IK1105-12 (12mm) · IK1105-15 (15mm) · IK1105-20 (20mm) · IK1105-25 (25mm) · IK1105-32 (32mm) · IK1105-40 (40mm) · IK1105-50 (50mm) |
| Cv Value (by orifice) |
4.5 / 4.5 / 9.3 / 12 / 24 / 29 / 48 |
| Performance |
|
| Operating Pressure |
0.05 ~ 1.6 MPa |
| Min. Pressure |
0.05 MPa |
| Medium |
Water |
| Medium Temperature (NBR seal) |
−10℃ ~ +80℃ |
| Medium Temperature (EPDM seal) |
−30℃ ~ +120℃ |
| Medium Temperature (VITON seal) |
−30℃ ~ +150℃ |
| Electrical |
|
| Supply Voltage |
DC 12/24V; AC 24/120/240V (60 Hz); AC 110/220V (50 Hz) |
| Voltage Tolerance |
±10% |
| Coil |
S21B; 20 VA (AC) / 18 W (DC); 100% ED; IP65 |
| Materials |
|
| Body |
Brass or stainless steel |
| Seals |
NBR / EPDM / VITON |
| Armature Tube |
Stainless steel 304 |
| Plunger / Stop |
Stainless steel 430F |
| Springs |
Stainless steel 304 |
| Shading Rings |
Copper |
| Dimensions (mm) |
|
| IK1105-12 (3/8") |
A=75, B=48, C=124, D=13 |
| IK1105-15 (1/2") |
A=75, B=60, C=124, D=13 |
| IK1105-20 (3/4") |
A=83, B=56, C=134, D=16 |
| IK1105-25 (1") |
A=100, B=72, C=145, D=20 |
| IK1105-32 (1-1/4") |
A=130, B=96, C=165, D=26 |
| IK1105-40 (1-1/2") |
A=130, B=96, C=165, D=26 |
| IK1105-50 (2") |
A=157, B=122, C=178, D=34 |
5. Applications
The IndusKey IK1105 is engineered for fire protection and water control duties:
-
Fire Fighting Systems: Main and zone isolation valves in fire protection networks.
-
Fire Sprinkler Lines: Wet/dry sprinkler system water supply control.
-
Deluge Valve Control: Pilot and control circuits for deluge systems.
-
Hose Reel Systems: Water supply switching for fire hose reel installations.
-
Industrial Fire Protection: Fire water circuits in petrochemical, power, warehouse and manufacturing facilities.
-
Water Control Circuits: General high-pressure water isolation requiring manual override capability.
6. Selection, Ordering & Installation Guidelines
Model Code System
The full valve is configured by a 7-field code — example: IK1105-32GSN S21B1 (32mm orifice, 1-1/4" G-thread, stainless steel body, NBR seal, S21B coil, AC220V)
| Type |
IK1105 |
Series, fire control valve |
| Orifice |
12 / 15 / 20 / 25 / 32 / 40 / 50 |
Orifice (mm) — matches port size (12: 3/8" … 50: 2") |
| Port Thread |
G / N |
G: BSPP · N: NPT |
| Body |
B / S |
B: Brass · S: Stainless steel |
| Seal |
N / E / V |
N: NBR · E: EPDM · V: VITON |
| Coil |
S21B |
Standard coil |
| Voltage |
1–6 |
1: AC220V · 2: DC24V · 3: AC110V · 4: DC12V · 5: AC24V · 6: DC6V |
Note: BSPT, flange and UNF connections are also available — confirm at order.
Selection
-
Function check: Confirm the required de-energized state with your fire system design — the IK1105 maintains open when de-energized per manufacturer specification.
-
Pressure: Full series 0.05–1.6 MPa; verify minimum system pressure ≥ 0.05 MPa.
-
Temperature: NBR (80°C) / EPDM (120°C) / VITON (150°C).
-
Body: Brass for standard installations; stainless steel for corrosive or coastal environments.
-
Size: Match orifice/port to flow (Cv table) and check A/B/C/D dimensions for installation clearance.
Installation
-
Orientation: Coil upright preferred; observe flow-direction arrow.
-
Manual override access: Position the valve so the override knob remains accessible for emergency operation and testing.
-
Piping: Flush pipelines before commissioning; fit a strainer upstream to protect the seat from debris — critical in fire systems where reliability is paramount.
-
Protection: IP65 coil suits indoor and outdoor installation; verify the installation meets local fire codes (the valve complements, not replaces, listed fire protection components).
Operation & Maintenance
-
100% ED rated for continuous energization.
-
Regular functional testing is essential in fire service: exercise the manual override and verify the de-energized open state per the fire system's inspection schedule.
-