1. Product Overview
The IndusKey IK1101 is a compact, pilot-operated piston solenoid valve engineered for normally closed 2/2-way control of steam, hot water and oil in space-constrained installations. Combining low power consumption with a corrosion-resistant stainless-steel body and steam-durable PTFE or VITON sealing, the IK1101 delivers reliable long-term pipeline service in a space-saving form factor for port sizes 1/2" to 1".
Designed for continuous pipeline duty, the IK1101 covers port sizes 1/2", 3/4" and 1" with orifice options of 5, 10 and 15 mm, an operating pressure range from 0 to 1.0 MPa with no minimum pressure differential required, and media temperatures up to 200°C with PTFE seals. The IP65-rated S21B coil (20 VA AC / 18 W DC, 100% ED) with universal AC/DC voltage options makes the IK1101 an ideal choice for compact fluid control on steam pipelines, hot water circuits, oil lines and industrial process equipment where installation space is limited.
2. Working Principle
The IK1101 employs a pilot-operated piston construction. Media pressure is used to actuate the main piston, allowing the solenoid to control flow with low electrical power input:
-
Pilot stage — When the coil is energized, the pilot orifice opens, allowing line pressure to act on the piston.
-
Main stage — The pressure-assisted piston actuates the main valve assembly: line pressure provides the bulk of the actuating force, so a compact, low-power coil can reliably switch the flow with minimal electrical demand.
-
Sealing — PTFE or VITON seal materials are selected for extended service in steam environments (PTFE to 200°C, VITON to 150°C), maintaining sealing integrity under elevated temperatures.
The IK1101 is a normally closed (NC) valve — it opens when the coil is energized and closes automatically when de-energized. With a specified operating pressure from 0 MPa to 1.0 MPa, the valve starts reliably even at zero pressure differential, accommodating low-pressure and gravity-fed systems where conventional pilot valves cannot operate.
3. Key Features & Competitive Advantages
A. Space-Saving Compact Design
B. Corrosion-Resistant Stainless Steel Construction
-
Stainless-steel body and wetted internals (armature tube SS304, plunger and stop SS430F, springs SS304, copper shading rings) resist corrosion in steam, hot water and oil service, extending service life in humid and aggressive environments.
C. Low Electrical Demand
D. Zero Minimum Pressure — Operates from 0 MPa
E. Steam Compatibility
F. Wide Temperature Options
G. Three Orifice / Four Body Options
H. 100% Duty IP65 Coil
-
S21B coil, 20 VA (AC) / 18 W (DC), 100% ED continuous energization, IP65 enclosure for dust-tight and water-jet protection.
I. Standard Threaded Ports
4. Technical Specifications
| Configuration |
|
| Valve Type |
2/2-way, pilot-operated piston, compact |
| Function |
Normally closed (NC) |
| Port Size |
1/2", 3/4", 1" |
| Connection |
BSPP (G), NPT threaded |
| Orifice |
5 / 10 / 15 mm |
| Models |
IK1101-05 (5mm, 1/2") · IK1101-10 (10mm, 1/2") · IK1101-15 (15mm, 3/4") · IK1101-25 (15mm, 1") |
| Cv Value |
0.5 (5mm) / 2.8 (10mm) / 2.8 (15mm) |
| Performance |
|
| Operating Pressure |
0 ~ 1.0 MPa (AC and DC) |
| Min. Pressure Differential |
0 MPa — no minimum required |
| Medium |
Steam, hot water, oil |
| Medium Temperature (PTFE seal) |
−60℃ ~ +200℃ |
| Medium Temperature (VITON seal) |
−30℃ ~ +150℃ |
| Electrical |
|
| Supply Voltage |
DC 12/24V; AC 24/120/240V (60 Hz); AC 110/220V (50 Hz) |
| Voltage Tolerance |
±10% |
| Coil |
S21B; 20 VA (AC) / 18 W (DC); 100% ED; IP65 |
| Materials |
|
| Body |
Stainless steel |
| Seals |
PTFE or VITON |
| Armature Tube |
Stainless steel 304 |
| Plunger / Stop |
Stainless steel 430F |
| Springs |
Stainless steel 304 |
| Shading Rings |
Copper |
| Dimensions (mm) |
|
| IK1101-05 (1/2", 5mm) |
A=50, B=30, C=75, D=16 |
| IK1101-10 (1/2", 10mm) |
A=70, B=30, C=82, D=16 |
| IK1101-15 (3/4", 15mm) |
A=80, B=40, C=92, D=19 |
| IK1101-25 (1", 15mm) |
A=80, B=40, C=92, D=19 |
5. Applications
The IndusKey IK1101 is engineered for compact, reliable fluid switching across industrial utility and process systems:
-
Steam Pipelines: Compact steam on/off control for distribution lines, tracing systems and process equipment.
-
Hot Water Circuits: Heating systems, hot water supply and heat-exchanger isolation in confined plant rooms.
-
Oil Lines: Lubricating oil and fuel oil line switching where space and corrosion resistance matter.
-
Low-Pressure Systems: Gravity-fed and low-pressure lines benefitting from 0 MPa start-up capability.
-
Compact Fluid Control: OEM machinery, skid-mounted systems and equipment cabinets with limited installation space.
-
Continuous Pipeline Systems: Long-term energized installations thanks to the 100% ED coil rating.
-
Industrial Process Equipment: Textile machines, food & beverage equipment, sterilizers and washing machinery requiring steam-rated solenoid control.
-
Corrosive Environments: Humid, washdown or mildly corrosive atmospheres benefiting from the stainless-steel body and internals.
6. Selection, Ordering & Installation Guidelines
Model Code System
The full valve is configured by a 7-field code — example: IK1101-25GSN S21B1
| Type |
IK1101 |
Series, NC pilot piston |
| Orifice |
05 / 10 / 15 / 25 |
05: 5mm–1/2" · 10: 10mm–1/2" · 15: 15mm–3/4" · 25: 15mm–1" |
| Port Thread |
G / N |
G: BSPP (G-thread) · N: NPT |
| Body |
B / S |
B: Brass · S: Stainless steel |
| Seal |
P / V |
P: PTFE · V: VITON |
| Coil |
S21B |
Standard coil |
| Voltage |
1–6 |
1: AC220V · 2: DC24V · 3: AC110V · 4: DC12V · 5: AC24V · 6: DC6V |
Note: Threaded BSPT connections are also available — confirm at order.
Selection
-
Function: The IK1101 is normally closed only; for normally open requirements consider the IK1100 series.
-
Pressure: Full operating range 0–1.0 MPa with no minimum differential — suitable for both low-pressure and standard pipeline conditions.
-
Temperature: Select PTFE seals for media above 150°C (up to 200°C); select VITON for −30℃ ~ +150℃ service.
-
Size: Match port size and orifice to required flow using Cv values; refer to the dimensions table for installation clearance.
-
Voltage: Specify coil voltage and frequency at order using the voltage codes above; ±10% supply tolerance applies.
Installation
-
Orientation: Install with the solenoid coil vertically upward where possible; ensure flow direction matches the arrow on the valve body.
-
Piping: Flush pipelines before installation to remove welding slag and debris; install a strainer upstream for steam/oil service.
-
Protection: The IP65 coil suits outdoor and washdown areas; protect from direct steam impingement and excessive radiant heat.
-
Wiring: Connect per coil terminal markings with a suitable cable gland to maintain IP65 integrity.
Operation & Maintenance
-
Rated for continuous (100% ED) energization; no duty-cycle limitation applies.
-
Periodically inspect seals and pilot orifice cleanliness in steam service; upstream filtration and proper water treatment prevent scale-related malfunction.